sonda-zigbee-per-corrente-continua-ad-effetto-hall-zed-icc-m-1

ZED-ICC-M

ZigBee Hall Effect Sensor for direct current measurements

  • Hall effect sensor for direct current measurements
  • Range between 0 and 1000A
  • Simple and quick installation, without services interruptions
  • Alarm thresholds
  • Sampling and transmission rates are confi gurable
  • Battery powered
  • Internal antenna

btm-scarica-scheda-en
btm-richiedi-info-en

ZigBee Hall Effect sensor ZED-ICC-M for direct current measurements

The ZED-ICC-M sensor is a battery supplied device that measures direct current through the Hall effect and regularly sends the collected information toward one of the 4-noks range Gateways. The measure is based onto the magnetic effect caused by the passage of the electric current in a conductor. To use the sensor, the bottom of the device has to be close to the conductor under current keeping a distance as larges as greater is the current to measure. The range is included between 0 to 1000A and dipends by the distance of the sensible element of the conductor under current.

Is possible to set the device in order to manage alarms to ring when its limits are trespassed, because of an exceeding value or of a too small value. It is also possible to schedule the sampling timing and the sending modalities of the measurements in order to increase the duration of the battery.

Technical Specs
General characteristics
Chip Ember EM250
Compatible IEEE 802.15.4
Stack EmberZnet 3.5.x (ZigBee PRO)
Modbus/RTU
Address settable through internal dip-switch
Mounting on a conductor set under the current to measure
RF characteristics Frequency: 2405 MHz ÷ 2480 MHz
Modulation: DSSS
Nominal transmission power: 2mW (3 dBm)
Receiver sensitive: -95 dBmm
Internal antenna gain: 0 dB
Outdoor/indoor range: 100m/30m
Supply High Energy Density AA 3,6V/2000mAh Lithium Battery
Battery duration: 3 years for data transmission every minute at 20°C
Current sensor
Hall effect sensor CSA-1V type
Non linearity error <1% Sensitive 280 V/T
Linear measurement range -5 mT ÷ +5 mT
Reply < 6μs
Measures expressed in Ampere tenths
Environment parameters Operation temperature: -10 ÷ +60°C; <80% U.R. non condensing
Storage temperature: -20 ÷ +70°C; <80% U.R. non condensing
Degree of protection: IP 55
Compliant with 2006/95/EEC, 89/336/EEC, 99/5/EEC directives
Reference Norms:
ETSI EN 300 328: Radio Compatibility for digital wide band transmissions
ETSI EN 301 489: Radio Compatibility
EN 61000-6-2: Electromagnetic Compatibility – Emissions
EN 61000-6-3: Electromagnetic Compatibility – Immunity
EN 60950-1: Electric Security